Medium-Voltage Cable Joint Selection Guide

Younxin Engineering Team · · Updated: August 26, 2026 · 2 min read · 385 words

Quick answer: Select a joint from both cable ends. Confirm that the two cables have compatible voltage class, conductor, insulation dimensions, screen/armour construction and bonding requirements before choosing a kit.

Information required before selection

A joint connects two complete cable systems, so data is required for Cable A and Cable B.

  • U0/U (Um) and cable standard for both sides
  • Conductor material, class, size and diameter for both sides
  • Insulation diameter over conductor and over insulation
  • Metallic screen type and cross-section
  • Armour and outer-sheath construction
  • Direct-buried, tray, tunnel, duct or submerged environment
  • Bonding, link-box and sheath-voltage requirements

Technical selection framework

Review areaWhat the buyer should confirmWhy it changes the supply
Conductor connectorConfirm material combination, size range and installation method.Cu-Cu, Al-Al and transition connections require different review.
Electrical interfaceMatch insulation diameter and stress-control range on both cables.Equal cross-section does not guarantee equal insulation dimensions.
Screen continuityRebuild the metallic screen with adequate current capability.Screen treatment affects fault-current path and induced voltages.
Armour/sheathRestore mechanical protection and environmental sealing.Direct burial and wet environments demand careful outer protection.
Bonding arrangementConfirm single-point, both-end or cross-bonded system requirements.Incorrect bonding can create sheath voltages or circulating currents.
  1. Collect both cable datasheets.
  2. Compare every construction layer.
  3. Define conductor and screen connection.
  4. Select stress-control and outer-seal system.
  5. Approve installation method, inspection and test plan.

Common RFQ mistakes

  • Assuming both 240mm² cables have identical dimensions.
  • Omitting screen-wire cross-section and fault duty.
  • Ignoring aluminium-to-copper transition requirements.
  • Ordering a standard straight joint for a special bonding system.

What a quotation package should contain

The joint submission should include compatibility range for both cables, connector, stress-control components, screen/armour continuity, outer protection, installation dimensions, instructions and type-test references.

Need equipment matched to your project?

Get a Quote →

Project-based example

When an existing cable is joined to a replacement cable from another manufacturer, a dimensional comparison sheet is often more important than the trade name. This should be completed before the outage or installation window.

Standards note: IEC 60502-4 may apply within its voltage scope. Special bonding, transition or repair joints need project-specific engineering beyond a standard kit code.

Technical content reviewed byMoyao LiaoYounxin project procurement documentation review

Younxin Engineering Team

Power Systems Engineering & Procurement Team

15+ years of project sourcing and OEM/ODM experience across transmission, distribution, substations, cable systems and power equipment.

Related Products

You May Also Like

Ready to Source Power Equipment for Your Project?

Get an initial response within 1 hour during business hours →

Need Power Project Support?

Products · Quotation · Technical Support

BOM
List
Drawing Catalog Alternatives WhatsApp