How to Select 10–35kV Cable Termination Kits

Younxin Engineering Team · · Updated: August 26, 2026 · 2 min read · 389 words

Quick answer: A termination kit must match the full cable construction and the equipment interface. Voltage class and conductor cross-section are necessary but not sufficient.

Information required before selection

Use the manufacturer’s cable datasheet or a measured cable construction sheet.

  • Rated voltage expressed as U0/U (Um)
  • Single-core or three-core construction
  • Copper or aluminium conductor and conductor class
  • Cross-section and conductor diameter
  • XLPE/EPR insulation diameter and screen construction
  • Armour, sheath material and overall diameter
  • Indoor/outdoor/switchgear/transformer interface and available space

Technical selection framework

Review areaWhat the buyer should confirmWhy it changes the supply
Voltage designationMatch U0/U (Um) and system grounding.Nominal labels such as “33kV” can refer to different cable designations.
Stress controlConfirm insulation diameter and applicable range.Electrical stress control acts at the screen cut and must fit the cable.
Conductor connectionMatch material, cross-section, class and lug/connector interface.A cable kit can be correct while the supplied lug is wrong.
Environmental sealReview indoor/outdoor exposure, pollution, UV, humidity and altitude.Sheds, creepage and sealing details vary by installation.
Equipment interfaceConfirm bushing, switchgear compartment and phase spacing.Termination length and lug orientation must fit the equipment.
  1. Identify the exact cable construction.
  2. Define the equipment and installation environment.
  3. Select termination technology and range.
  4. Confirm lugs, grounding, breakout and sealing components.
  5. Review preparation dimensions and installation instructions.

Common RFQ mistakes

  • Ordering “35kV 240mm² termination” without a cable datasheet.
  • Confusing 18/30(36)kV with another voltage designation.
  • Ignoring wire-screen quantity or armour grounding.
  • Failing to confirm indoor/outdoor and equipment clearances.

What a quotation package should contain

The supplier should provide the kit designation, cable applicability range, component list, preparation dimensions, installation instructions, lug/connector details, grounding components, packing labels and test-document scope.

Need equipment matched to your project?

Get a Quote →

Project-based example

For a 36(42)kV accessory package, the same conductor size required separate confirmation for single-core outdoor terminations and straight-through joints. Core construction and installation position were treated as independent selection fields.

Standards note: IEC 60502-4 is commonly referenced for accessories used with extruded-insulation power cables up to 30kV (Um 36kV). Confirm the exact project voltage designation and required test scope.

Technical content reviewed byMoyao LiaoYounxin project procurement documentation review

Younxin Engineering Team

Power Systems Engineering & Procurement Team

15+ years of project sourcing and OEM/ODM experience across transmission, distribution, substations, cable systems and power equipment.

Related Products

You May Also Like

Ready to Source Power Equipment for Your Project?

Get an initial response within 1 hour during business hours →

Need Power Project Support?

Products · Quotation · Technical Support

BOM
List
Drawing Catalog Alternatives WhatsApp